Upgrade Solution for Fire Safety System Hindered by Asbestos Issue

Slide Note
Embed
Share

Fire safety audit identified a need to upgrade an outdated fire system in supported living accommodation. Asbestos presence delayed the project, requiring new solutions for maintaining fire safety. Implementation of a wireless RF system was proposed as a cost-effective and efficient solution, meeting audit requirements and ensuring property compliance with futureproofing measures. Detailed product requirements and installation notes were provided for the proposed system.


Uploaded on Sep 28, 2024 | 0 Views


Download Presentation

Please find below an Image/Link to download the presentation.

The content on the website is provided AS IS for your information and personal use only. It may not be sold, licensed, or shared on other websites without obtaining consent from the author. Download presentation by click this link. If you encounter any issues during the download, it is possible that the publisher has removed the file from their server.

E N D

Presentation Transcript


  1. Asbestos Issue Prevents Fire Safety Upgrade Kevin Thomas, Peter O Connell, Peter Lewis, Steve Paskell, Martyn Walley Jan 15

  2. Introduction Fire Safety Audit Review to upgrade Historical Fire System within Supported Living Accommodation None Compliance / Original Installation >30 Years Costing & Design Required for Replacement Hardwire System Tender Completed & Contractor Appointed Full Asbestos Survey conducted on Property Start Delay due to Historical Issue Asbestos on site Solutions now required to be sought to maintain Fire Safety at property should system fail Aico consulted for possible solutions due to previous projects completed with Tai Calon

  3. Solution Wireless / RF System Cost effective solution minimising site disruption Meet requirements of both Audit & H&S Report System Specification Design Drafted utilising new product providing Integration In House Electrical Team Quick, Cost Effective Solution, PPM Maintaining Coverage of New & Existing System Enforcing Stay Put Policy with Visual Aid within Property Futureproofing System DDA Compliance Warden Call Integration Duplex Communication with House Fire Panel Presentation conducted with Tai Calon & South Wales Fire & Rescue Service Nov 14 Internal & External buy in gained for System Installation

  4. Ground Floor East 4 x Ei414 1 x Ei603TYCRF 3 x Ei605TYWRF 8 x SAB300R 8 x Ei428 Zone 2 Zone 1

  5. First Floor West 1 x Ei603TYCRF 7 x Ei605TYWRF 8 x SAB300R 8 x Ei428 Zone 3

  6. Product Requirements Quantity Product Code Device 3 Ei603TYCRF 10Year Battery RadioLINK Optical Alarm 25 Ei605TYWRF 10Year Battery RadioLINK Heat Alarm 4 Ei414 Fire / CO Alarm Interface 1 Ei208WRF RadioLINK CO Alarm 31 Ei428 RadioLINK Relay Module 31 SAB300 Strobe Light Red

  7. Ei 414 Integration with Part 1 Panel Either + & - from sounder cct Or volt free change over op driven from Fire Panel C N/O N/C 470 ohm } 10-30VDC C N/O N/C E O L Or C N/O N/C } 230VAC Zone 1 - 4 INSTALLATION NOTES; - Each Ei414 to be wired as above per Zone - Due to Limited Zone availability on the Panel, CO will sound the Same Circuit as the Fire Notification - Fire Alarm Trigger to the Ei414 can be either a Volt-free change over or triggered from the Sounder Circuit - Power Supply for the Ei414 can be either 230VAC or fed from the Fire Panel - The EOL resistor if not local can be substituted for the outgoing circuitry - The Fault Resistor 470 Ohm is indicative only as you will need to verify this from the existing panel on site 4 x Ei414 units cabled individually to 4 Zone from the respective fire Panel

  8. Ei 414 External Functions Fire LED Indicator Service LED Indicator CO LED Indicator Functional Keyswitch Power LED Indicator RF LED Indicator House Code Button Underside

  9. Ei 414 Key Switch Function s In the OFF Position; all functions from the Ei414 are disabled No Functional Relays will Operate OFF In the ON Position; all functions from the Ei414 are enabled Any activation via actual Smoke, CO, Service or other optional Input will operate the appropriate Relay and LED Any manual operation of a Test button from a coded device will NOT activate the relays or follow on functions. ON In the TEST Position; all functions from the Ei414 are enabled Any activation via actual Smoke, CO, Service or other optional Input will operate the appropriate Relay and LED Any manual operation of a Test button from a coded device will also activate the relays or follow on functions. TEST NOTE: The system MUST be house coded to differentiate between a Fire & CO RF Signal Type s

  10. Ei414 Live Schemes City of Swansea County Council Newly Specified Scheme for refit currently out to Tender Carmarthenshire County Council 3 Schemes currently out to Tender Integration with Main Fire Panel & Deaf Alert Equipment Hafod HA / Hendre HA 5 New Schemes TAFF HA Red Sea House Warden Call Integration Installed

  11. Maintenance Daily Checks Scheme Manager Visual Inspection Weekly Checks Completed by Scheme Manager Sample Test on Fire Alarm Devices Log Book Completed Any Faults Recorded and reported to Tai Calon Monthly Checks Tai Calon Competent Person Attendance Fire Alarm Test Emergency Lighting Test Log Book & Work Sheets Completed Any Faults Reported & Rectified Immediately Essential Stocks Held in house

Related