Energy Performance Index for Commercial Buildings

Energy performance of
Indian Commercial buildings
 
Outline
 
What is energy performance index for
commercial buildings
Commercial building energy performance
ECO-III Benchmarking study
IGBC rated buildings
BEE star rated buildings
What is energy performance
index for commercial
buildings
Source: BEE Star rating for Office Building & BEE Star rating for BPO
Main
Meter
 
Renewable
electricity
 
Grid
Electricity
 
DG
Electricity
 
Built-up area (m
2
)
 
 
 
 
Total
electricity
EPI of Commercial Building
(2011)
 
Source: ECO-III Study on “Energy use in commercial buildings – National benchmarking study” (2011)
149
349
115
258
141
88
378
279
252
One Shift Office
Buildings (149)
Three Shift Office
Buildings (349)
4 & 5 Star
Hotels (279)
Multi Specialty
Hospitals (378)
Shopping
Malls (252)
EPI of Office Buildings
 
Sources:
- ECO-III Benchmarking study
- IGBC rated buildings
- BEE star rated buildings
BEE Star Rating for office
building
 
180
 
155
 
130
 
105
 
80
EPI of IGBC rated office
buildings
Do not qualify for
BEE star rating
Do not get good
BEE star rating
EXAMPLES OF ENERGY
EFFICIENT OFFICE BUILDING
 
Institute of Rural Research and
Development (IRRAD), Gurgaon
 
Day-use office building
Built-up area: 7069 m
2
EPI: 48 kWh/m
2
.y
Source: Ashok B Lall Architects
Infosys, SDB 1, Pocharan
Campus, Hyderabad
 
Day-use office building
Built-up area: 11,600 m
2
EPI: 86 kWh/m
2
.y
Source: Infosys (2011-12 data)
Infosys Journey towards
Energy Efficiency
Source: Infosys
BPO BUILDINGS
 
Performance indicator for
BPO
Annual Average hourly Energy Performance
Index (AAhEPI) (Wh/h.m
2
)
BEE Star Rating for BPO
building
 
35
 
30
 
25
 
20
 
15
Performance of BEE Star BPO
Buildings & IGBC rated Tech
Parks
Do not qualify for BEE star rating
Source: BEE Star rating of BPO buildings (2011 data) & IGBC rating for Tech Parks (2012 data)
Summing up
 
Green rating may not be sufficient to ensure
energy efficiency in the buildings
Need for absolute benchmarking for energy
performance
Type of building
Performance indicator (AAhEPI OR EPI)
Start with high energy performance
benchmarks (e.g. BEE 5-star rating OR best
energy efficient buildings)
THANK YOU !
 
Slide Note
Embed
Share

Energy Performance Index (EPI) is a key metric used to evaluate the energy efficiency of commercial buildings. It is calculated based on the annual grid electricity consumption, annual DG electricity consumption, and the built-up area of the building. Various studies and ratings such as ECO-III Benchmarking, IGBC ratings, and BEE star ratings provide benchmarks for different types of commercial buildings. The EPI values indicate the energy efficiency levels of buildings, with lower values representing better performance. Additionally, the EPI can help in determining eligibility for BEE star ratings and assess the energy usage of different building types.

  • Energy Performance Index
  • Commercial Buildings
  • ECO-III Study
  • BEE Star Ratings
  • Energy Efficiency

Uploaded on Sep 27, 2024 | 0 Views


Download Presentation

Please find below an Image/Link to download the presentation.

The content on the website is provided AS IS for your information and personal use only. It may not be sold, licensed, or shared on other websites without obtaining consent from the author. Download presentation by click this link. If you encounter any issues during the download, it is possible that the publisher has removed the file from their server.

E N D

Presentation Transcript


  1. What is energy performance index for commercial buildings Commercial building energy performance ECO-III Benchmarking study IGBC rated buildings BEE star rated buildings

  2. Renewable electricity Grid Total electricity Main Meter Electricity DG Electricity Built-up area (m2) Energy Performance Index (EPI) (kWh/m2.y) =Annual Grid Electricity + Annual DG Electricity Built up area Source: BEE Star rating for Office Building & BEE Star rating for BPO

  3. 378 Multi Specialty Hospitals (378) 349 Three Shift Office Buildings (349) 279 4 & 5 Star Hotels (279) 258 252 Shopping Malls (252) 149 141 One Shift Office Buildings (149) 88 115 Source: ECO-III Study on Energy use in commercial buildings National benchmarking study (2011)

  4. Sources: - ECO-III Benchmarking study - IGBC rated buildings - BEE star rated buildings

  5. 180 155 130 105 80

  6. Do not qualify for BEE star rating Do not get good BEE star rating

  7. Day-use office building Built-up area: 7069 m2 EPI: 48 kWh/m2.y Source: Ashok B Lall Architects

  8. Day-use office building Built-up area: 11,600 m2 EPI: 86 kWh/m2.y Source: Infosys (2011-12 data)

  9. Source: Infosys

  10. Annual Average hourly Energy Performance Index (AAhEPI) (Wh/h.m2) EPI (kWh/m2.y) x 1000 Annual hours of operation AAhEPI (Wh/h.m2) =

  11. 35 30 25 20 15

  12. Do not qualify for BEE star rating Source: BEE Star rating of BPO buildings (2011 data) & IGBC rating for Tech Parks (2012 data)

  13. Green rating may not be sufficient to ensure energy efficiency in the buildings Need for absolute benchmarking for energy performance Type of building Performance indicator (AAhEPI OR EPI) Start with high energy performance benchmarks (e.g. BEE 5-star rating OR best energy efficient buildings)

Related


More Related Content

giItT1WQy@!-/#giItT1WQy@!-/#giItT1WQy@!-/#giItT1WQy@!-/#giItT1WQy@!-/#giItT1WQy@!-/#