Buckingham Park Water District Tracer Study by Guy Schott: Detailed Analysis

Slide Note
Embed
Share

Detailed analysis and findings from a tracer study conducted on 2/10/16 at Buckingham Park Water District by Guy Schott. The study includes information on the 200K Clearwell, outlet configurations, baffle heights, nozzle velocities, chlorine residual levels, and more. Insights on flow rates, dosage, baffling factor, and tank chlorine levels are provided, highlighting key observations and measurements. Visual data and images further support the comprehensive analysis of the water district's operational parameters.


Uploaded on Sep 11, 2024 | 0 Views


Download Presentation

Please find below an Image/Link to download the presentation.

The content on the website is provided AS IS for your information and personal use only. It may not be sold, licensed, or shared on other websites without obtaining consent from the author. Download presentation by click this link. If you encounter any issues during the download, it is possible that the publisher has removed the file from their server.

E N D

Presentation Transcript


  1. Buckingham Park Water District Tracer Study 2/10/16 By Guy Schott

  2. 200K Clearwell 30-ft Diameter; 37.8 ft. Baffle Height

  3. 2 ft opening Outlet Outlet Flush 18-in opening, 6-in pipe Inlet Diameter: 30 ft Baffle Ht: 37.8 ft Nozzle Velocity: 5.1 ft/sec Inlet Riser 12 ft ht, 6" x 4" Reducer

  4. Nozzle Velocity: 5.1 ft/sec Baffle Curtain Inlet Riser 12 ft Ht. 6 x 4 Reducer

  5. Inlet Side of Clearwell

  6. Inlet Side of Clearwell Baffle Curtain

  7. Flow

  8. Outlet

  9. Outlet Side of Clearwell Leaking baffle

  10. Outlet Leaking baffle

  11. Outlet

  12. time min 0 15 30 45 60 75 90 105 120 130 140 Tracer mg/L 0 0.019 0.125 0.177 0.27 0.322 0.398 0.407 0.592 0.598 0.639 t/T 0.00 0.02 0.03 0.05 0.07 0.09 0.10 0.12 0.14 0.15 0.16 Baffling Factor: 0.13 Dosage: 4.6 Flow (inlet/outlet): 200 gpm; HRT: 867 minutes (14.4 hrs)

  13. Clearwell Chlorine Residual Depth Operating Tank Level: 31.8 ft. 31 ft 1.82 mg/L 1.81 mg/L 16.5 ft 1.73 mg/L 1.81 mg/L 1.86 mg/L 1.5 ft 1.73 mg/L Inlet Side Outlet Side