Outdoor air conditioning units in San Francisco must adhere to specific location requirements to address noise concerns and property line distances. The recent code emphasizes split heat pump systems for efficiency and reduced carbon footprint. Check the San Francisco Police Code Article 29 for noise regulations.


Uploaded on Jul 23, 2024 | 0 Views


Download Presentation

Please find below an Image/Link to download the presentation.

The content on the website is provided AS IS for your information and personal use only. It may not be sold, licensed, or shared on other websites without obtaining consent from the author. Download presentation by click this link. If you encounter any issues during the download, it is possible that the publisher has removed the file from their server.

E N D

Presentation Transcript


  1. 2022 San Francisco Mechanical Code (SFMC) Air Conditioning Unit Location Requirement Mechanical Plan Review Section, SFDBI August 8, 2022

  2. Outdoor condenser units can emit up to 82 dB, depending on the models. With the current All-Electric requirement for new construction buildings (SFBC 106A.1.17) https://codelibrary.amlegal.com/codes/san_francisco/latest/sf_buildin g/0-0-0-92027 , the number of buildings with split heat pump systems has greatly increased. Split heat pump systems have an outdoor condenser component. DBI has also seen an increase in the number of existing residential buildings being provided with split heat pump systems due to heat pump systems being highly efficient, providing both heating and cooling, and having a reduced carbon footprint. Until the recent code change, the most common space conditioning system installed in San Francisco for residential dwelling units were furnaces, which typically have no outdoor component. The property line distance requirement, combined with the current San Francisco Police Code Article 29: Regulation of Noise, is proposed to help mitigate noise concerns from neighboring residents. Reasons for Outdoor Air Conditioning Unit Location Requirements

  3. 2022 CMC Section 308: 308.0 Improper Location. 308.1 General. Piping or equipment shall not be so located as to interfere with the normal use thereof or with the normal operation and use of windows, doors, or other required facilities. The proposed code language to be added to 2022 SFMC section 308.2 to address the location of the outdoor air conditioning unit. Proposed 2022 SFMC 308.2: 308.2The outdoor Air Conditioning unit shall not be located less than 5 feet from the property line. Refer to the San Francisco Police Code Article 29: Regulation of Noise for the noise limits due to the installation of an outdoor Air Conditioning unit. https://codelibrary.amlegal.com/codes/san_francisco/latest/sf_polic e/0-0-0-6461

  4. Example of Other Local Jurisdiction Requirements: City of Santa Clara

  5. Example of Other Local Jurisdiction Requirements: City of Palo Alto

  6. Example of Other Local Jurisdiction Requirements: City of Los Altos

  7. Example of Other Local Jurisdiction Requirements: City of Sunnyvale

  8. San Francisco Police Code Article 29: Regulation of Noise https://codelibrary.aml egal.com/codes/san_fr ancisco/latest/sf_police /0-0-0-6461