Weatherization Energy Auditor Single Family - Intermediate Math Curriculum
This curriculum from the Weatherization Assistance Program provides training in intermediate math skills for energy auditors working with single-family homes. Participants learn how to apply units of measurement, calculate areas and volumes, assess building tightness, and more to improve energy efficiency in residential buildings.
Download Presentation
Please find below an Image/Link to download the presentation.
The content on the website is provided AS IS for your information and personal use only. It may not be sold, licensed, or shared on other websites without obtaining consent from the author. Download presentation by click this link. If you encounter any issues during the download, it is possible that the publisher has removed the file from their server.
E N D
Presentation Transcript
WEATHERIZATION ENERGY AUDITOR SINGLE FAMILY Intermediate Math WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Learning Objectives INTERMEDIATE MATH By attending this session, participants will be able to: Apply units of measurement. Calculate areas and volumes. Assess building tightness limits. Calculate CFM50 vs. ACH. Estimate bags of cellulose. Calculate appropriate attic and foundation venting. Discuss refrigerator usage calculations for determining replacement eligibility. Calculate lighting retrofit savings. 2 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Typical Units INTERMEDIATE MATH Surface Area Volume Air Flow 3 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Floor Area INTERMEDIATE MATH Conditioned Unconditioned Image developed for US DOE WAP National Standardized Curricula 4 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Calculate Conditioned Area INTERMEDIATE MATH Area = Length x width Final units = Square feet Tackle floor plans in pieces. Reduce complicated shapes into small, simple shapes. Image developed for US DOE WAP National Standardized Curricula 5 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Calculate Conditioned Area INTERMEDIATE MATH 180 ft2 Main House 1 Stories Double area 128 ft2 416 ft2 16 x 26 = 416 ft2 + 416 ft2 1,140 ft2 12 x 15 = 180 ft2 128 ft2 16 x 8 = Image developed for US DOE WAP National Standardized Curricula 6 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Volume Keep the Units Straight INTERMEDIATE MATH Keep the units straight. Square Feet x Feet = Cubic Feet ft2x ft = ft3 Cubic Feet Feet = Square Feet = ft2 ft3 = ft2 ft Image developed for US DOE WAP National Standardized Curricula 7 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Calculate Conditioned Volume INTERMEDIATE MATH Main House, 2nd Fl = Attic Flat = 8 Eaves Wall = 3 Ell = 180 ft2x 7 6 = ___ Main House, 1st Fl = 416 ft2 x 8 = _ Rear Addition = 128 ft2x 7 5 = ___ Image developed for US DOE WAP National Standardized Curricula 8 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Keep the Units Straight INTERMEDIATE MATH 1 x 1 = 1 ft2 12 x 12 = 144 in2 = 1 ft2 300 x 200 = 60,000 in2 60,000 in2 = 417 ft2 144 in2/ft2 9 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Calculate Conditioned Volume INTERMEDIATE MATH Main House, 2nd Fl = Attic Flat = 8 Eaves Wall = 3 Ceiling Height = 7 Ell = 180 ft2x 7 6 = 1,350 ft3 Main House, 1st Fl = 416 ft2 x 8 = 3,328 ft3 Rear Addition = 128 ft2x 7 5 = 950 ft3 Image developed for US DOE WAP National Standardized Curricula 10 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Odd Shapes INTERMEDIATE MATH Area: Triangle = Base x Height Circle = r2 ; 3.14 Volume: (Area x 3rd Dimension) Triangle = Base x Height x Length Cylinder = r2 x Height Images developed for US DOE WAP National Standardized Curricula 11 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Conditioned Volume: 2nd Floor INTERMEDIATE MATH Tackle complex shapes. Break down into simple shapes. Main House, 2nd Fl = Attic Flat = 8 Eaves Wall = 3 Ceiling Height = 7 Second Story Image developed for US DOE WAP National Standardized Curricula 12 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Calculating Volume: 2nd Floor INTERMEDIATE MATH Top Rectangle = 8 ft x 4 ft x 26 ft = 832 ft3 *Volume of a triangle = Base x Height x Length 2 Triangles* = 2 x ( (4 ft x 4 ft) x 26 ft) = 416 ft3 2nd Floor Volume: 832 ft3 1,248 ft3 + 416 ft3 2,496 ft3 Bottom Rectangle = 16 ft x 3 ft x 26 ft = 1,248 ft3 Image developed for US DOE WAP National Standardized Curricula 13 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Calculate Conditioned Volume INTERMEDIATE MATH Total floor area x 8 can get you close: 1,140 ft2 x 8 ft = 9,120 ft3 Ell = 1,350 ft3 Rear Addition = 950 ft3 Main House, First floor = 3,328 ft3 Main House, Second floor = 2,496 ft3 TOTAL = 8,124 ft3 Image developed for US DOE WAP National Standardized Curricula 14 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Indoor Air Quality At Risk Calculation INTERMEDIATE MATH At Risk Calc: 8,400 ft3 minimum 2,100 ft3 for each occupant beyond 4 Compare to actual heated volume For Example: 5 occupants: 5 - 4 = 1 1 x 2,100 ft3 = 2,100 ft3 8,400 ft3 + 2,100 ft3 = 10,500 ft3 Our sample home with a volume of 8,124 ft3 is less than the 10,500 ft3 minimum, and is considered At Risk. 15 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Dividing by Fractions INTERMEDIATE MATH Dividing by a fraction is the same as multiplying by the reciprocal. 21 Reciprocal of is , or 2. 20 10 = 10 x = 10 x 2 = 21 10 20 = 10 x = 10 x 2 = 21 34 1.5 = x = = = 1 = 21 34 64 32 16 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Air Changes per Hour INTERMEDIATE MATH ACH50 = CFM50 x 60min/hr Volume Volume of conditioned space = 8,124 ft3 Blower door reading = 2,000 CFM50 ACH50 = 2,000 CFM50 x 60 / 8,124 ft3 14.77 Air Changes per Hour at 50 Pa = 17 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Percent Infiltration Reduction INTERMEDIATE MATH Percentage Reduction Goal If ACH50 = 11-17, goal is 25%. If ACH50 = 18-22, goal is 35%. If ACH50 > 23, goal is 40%. Example ACH50 = 14.77, goal is 25%. 100% - 25% = 75% of Pre-Weatherization CFM50 is goal. Pre-Weatherization 2,000 CFM50 2,000 CFM50 x 75% = 2,000 x 0.75 = 1,500 CFM50 18 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Estimating Attic Insulation INTERMEDIATE MATH Main house + Addition + Ell = Total attic area Main house attic = 8 * 26 = 208 ft2 Addition = 128 ft2 Ell = 180 ft2 Total attic area = 516 ft2 Bring attic from R-0 to R-40. 19 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Estimating Attic Insulation INTERMEDIATE MATH Sample Coverage Chart for Blown-In Cellulose R-Value @ 75 Mean Temp. Minimum Thickness (inches) Maximum Net Coverage (No adjustment for framing) Gross Coverage (based on 2 x 6 framing on 16 centers) To obtain a thermal resistance of: Installed insulation shouldn t be less than: Thickness after settling Max. Sq. Ft. per Bag Min. Bags per 1,000 Sq. Ft. Min. Weight per Sq. Ft. (lbs) Max. Sq. Ft. per Bag Min. Bags per 1,000 Sq. Ft. R-50 15.0 13.5 13.8 72.7 1.689 14.3 69.9 R-42 12.6 11.4 16.4 61.0 1.419 17.2 58.3 R-40 12.0 10.8 17.2 58.1 1.351 18.1 55.4 R-38 11.4 10.3 18.1 55.2 1.284 19.1 52.4 R-32 9.6 8.6 21.5 46.5 1.081 22.9 43.7 R-30 9.0 8.1 22.9 43.6 1.014 24.5 40.8 R-25 7.5 6.8 27.5 36.3 0.845 39.8 33.6 R-24 7.2 6.5 28.7 34.9 0.811 31.2 32.1 R-22 6.6 5.9 31.3 32.0 0.743 34.3 29.2 R-19 5.7 5.1 36.2 27.6 0.642 40.0 25.0 R-13 3.9 3.5 52.9 18.9 0.439 58.4 17.1 R-11 3.3 3.0 62.6 16.0 0.372 69 14.5 20 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Estimating Attic Insulation #1 INTERMEDIATE MATH Total Attic Area = 516 ft2 Bring Attic from R-0 to R-40 At R-40 w/ 2x6, 16 oc., 1 bag covers 18.1 ft2* Assume 15% waste allowance How many bags do you need for the attic? * From sample coverage chart 21 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Estimating Attic Insulation #2 INTERMEDIATE MATH Total attic area = 516 ft2 Bring attic from R-0 to R-40 516 ft2 1 bag/18.1 ft2 = 28.5 bags of insulation. Assume 15% waste allowance 28.5 x 1.15 = 32.78 bags = 33 bags (always round up). 22 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Keep the Units Straight INTERMEDIATE MATH Label units to keep track. Units on top and bottom cancel each other out. lbs ft3 x 1,000 ft3 = 3,500 lbs 3.5 lbs/ft3 x 1,000 ft3 = 3.5 bag 36 lbs 3,500 lbs 36 lbs/bag = 3,500 lbs x = 97.2 bags Avoid errors such as gallons of electricity! 23 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Estimating Wall Insulation INTERMEDIATE MATH Sample Wall Coverage Chart Maximum Coverage Square Feet per Bag Thickness (inches) Weight per Square Foot Sidewalls 16 O.C. 24 O.C. R-13 (2x4) 3.5 33.8 32.7 0.758 R-20 (2x6) 5.5 21.5 20.8 1.192 How many bags to dense-pack 1,200 ft2 of wall with 2 x 4 studs, 16 o.c.? 1,200 ft2= 35.5 bags = 36 bags 33.8 ft2/bag 24 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Estimating Wall Insulation INTERMEDIATE MATH What density does the chart assume? Maximum Coverage Square Feet per Bag Thickness (inches) Weight per Square Foot Sidewalls 16 o.c. 24 o.c. R-13 (2x4) 3.5 33.8 32.7 0.758 R-20 (2x6 5.5 21.5 20.8 1.192 Chart indicates 0.758 lbs/sq. ft. Each sq. ft. of wall contains: 1 ft x 1 ft x 3.5 inches = 0.2917 ft3 0.758 lbs/ft2= 2.6 lbs/ft 0.2917 ft3/ft2 12 in/ft 3 What? So low? Not really, that accounts for space taken up by framing 25 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Estimating Wall Insulation INTERMEDIATE MATH What if there s no coverage chart? The math is simple: How many bags to dense-pack 1,200 ft2 of wall with 2 x 4 studs, 16 o.c.? Assume 3.5 lbs/ft3 & 36 lbs/bag. 1,200 ft2 x 3.5 inches = 350 ft3 12 in/ft 350 ft3 x 3.5 lbs/ ft3 = 1,225 lbs 1,225 lbs = 34.03 bags = 35 bags 36 lbs/bag Same as the chart 26 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Calculate Wall Insulation: Sample House INTERMEDIATE MATH Unconditioned Conditioned Image developed for US DOE WAP National Standardized Curricula 27 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Estimate Wall Insulation: Sample House INTERMEDIATE MATH Main House 672 ft2 First Floor = 2(16 x 8 ) + 2(26 x 8 ) = Second Floor = 2(3 x 26 ) + 2(6 x 26 )* + 2(16 x 7 ) = Addition = 2(8 x 7 5 ) + (16 x 7 5 )** = Ell = (12 x 7 6 )***+ 2(15 x 7 6 ) = 692 ft2 237 ft2 315 ft2 * Sloped ceiling, from walk-through notes ** Only count one long wall, other wall abuts the home *** Only count one short wall, other wall abuts the home Images developed for US DOE WAP National Standardized Curricula 28 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Wall Insulation: Sample House INTERMEDIATE MATH Add total wall area 672 ft2 692 ft2 237 ft2 + 315 ft2 1,916 ft2 Subtract doors and windows Heated space windows & doors: 8 windows, 12.5 ft2 each 8 x 12.5 ft2 = 100 ft2 2 doors, 20 ft2 each 2 x 20 ft2 = 40 ft2 + - 140 ft2 Window & door area = 140 ft2 1,776 ft2 Wall area needing insulation = 29 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Estimating Wall Insulation: Sample House INTERMEDIATE MATH Sample Wall Coverage Chart Maximum Coverage Square Feet per Bag Thickness (inches) Weight per Square Foot Sidewalls 16 O.C. 24 O.C. R-13 (2x4) 3.5 33.8 32.7 0.758 R-20 (2x6 5.5 21.5 20.8 1.192 How many bags to dense-pack 1,776 ft2 of wall with 2 x 4 studs, 16 o.c.? 1,776 ft2= 52.5 bags = 53 bags 33.8 ft2/bag 30 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Attic Venting INTERMEDIATE MATH 1 ft2 NFA of vent needed for every 300 ft2 of attic* If vents are located high and low to induce ventilation, 1 ft2 of vent needed for every 600 ft2 of attic 1,000 ft2 attic with gable vents o 1,000 ft2 / 600 ft2 = 1.67 ft2 of vent needed o Two existing gable vents each 12 x 10 o 2 x 12 x 10 /144 = 1.67 ft2 of existing vent Is existing venting adequate? No, must use NFA. * Assumes ceiling vapor barrier. 31 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Foundation Venting INTERMEDIATE MATH 1 ft2 of vent needed for every 1,500 ft2 of crawl space 1,000 ft2 crawl space 1,000 ft2= 1,500 ft2 0.67 ft2 of vent needed 0.67 ft2 x 144 in2/ft2 = 96 in2 NFA 32 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Refrigerator Calculation INTERMEDIATE MATH If existing refrigerator is metered, kWh/year = Metered usage (kWh) hours year minutes hour x 60 x 8760 Metering duration (minutes) 0.882 0.882 is a factor to adjust estimated energy usage since the crew asks the client not to open and close the refrigerator during metering (Source: John Proctor). This does not include 7% for defrost cycle. 33 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Lighting Calculation INTERMEDIATE MATH To calculate the energy saved through lighting retrofits we need: Number of bulbs being replaced. Wattage of existing bulbs. Wattage of replacement bulbs. Usage (hrs/day). days year hours day Watts fixture kW x x 6 x 365 4 ftx (60-13) 1,000 Watts = 412 kWh/yr 34 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov
Summary INTERMEDIATE MATH Area (square feet) = length x width Volume (cubic feet) = length x width x height Label units to keep them straight. All area, volume, ACH and estimating calculations rely on basic functions: addition, subtraction, multiplication, and division. Estimating bags of cellulose requires knowledge of framing type (for walls), attic area and recommended R-values (for attics). Attic and foundation venting calculations need NFA of vents, not just vent dimensions. Refrigerator calculations in kWh/year determine cost-effectiveness of replacements. Lighting savings calculations are based on wattage differences. 35 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM December 2012 eere.energy.gov